13
DAILY USER´S MANUAL • EBL128 VERSION 2.2.X • DOCUMENT NUMBER: MEW01786 • REVISION: 1
9. PRESENT SYSTEM STATUS (H4)
Information only.
a) Log on to the c.i.e.
b) Navigate to menu H4.
c) Press "A". The sub menu consists of a list (U1 - U8) in which you can scroll. U1 is displayed.
d) Select a sub menu and press “A”.
9.1. SUB MENU LIST (U1 – U8)
Disablements, except "disablements by time channel", are
displayed.
Indicated by LED "Disablements".
Disablement by time channel
Only "disablements by time channel", are displayed.
Indicated by LED "Disablements", also the LEDs "Fault /
Disablements Alarm devices" and/or "Fire brigade tx".
Use the keypad to specify the "Start sensor".
The default zone-address 00-00 can be used.
Press "A". This is a list in which you can scroll.
NOTE! For most detectors additional information can be shown by
using .
Sensors activating service
signal
Indicated by LED "Service".
NOTE! Service signal is acknowledged via menu H8/S2, which
require log on with a password for access level "Service
personnel".
If one or more technical warnings are activated in the system, the
technical warning symbol [i] is shown.
Use the keypad to select event log:
- 0 = Alarm.
- 1 = Interlocking.
- 2 = General.
Press "A". This is a list in which you can scroll.
Version and alarm counter
- Version: The EBL128 software / firmware version.
- Alarm counter The alarm counter is increased with "1" every time
the c.i.e. enters the real "fire alarm condition".