Introduction
19
18
H
Battery terminals
H
Battery terminals
4 Technical Data
4.1 PV Input
4.2 AC Input/Output
Start input voltage [V]
Model
Max.recommended PV power [W]
15200
Max.MPPT power [W]
Max.DC voltage [V]
Norminal DC operating voltage [V]
Max. input current [A]
Max. short circuit current [A]
MPPT voltage range [V]
MPPT voltage range [V](full load)
11400
550
360
A:16/B:16/C:16
A:20/B:20/C:20
90-500
120
235-500
EVHB-I7
AFCI
No. of MPP trackers
Strings per MPP tracker
DC disconnection switch
3
Yes
Yes
A:1/B:1/C:1
Maximum output fault peak current
Model
Norminal AC power [VA]
7608
Max. apparent AC power [VA]
Rated grid voltage [V]
Rated grid Frequency [Hz]
Norminal AC current [A]
Max. Output Continuous current [A]
Maximum output fault current and
7608
240
50/60
31.7
48/90
515/5
EVHB-I7
Displacement power factor
Total harmonic distortion
Parallel operation
0.8 leading to 0.8 lagging
<3%
Yes
duration [A/ ms]
and duration [A/ ms]
31.7
(THD, rated power)
4.3 General Data
General
EVHB-I7
Dimensions with Safety Switch
Weight with Safety Switch [lb(KG)]
Cooling concept
33.1*15.7*5.7840*400*146
75 (34)
Natural convection with internal fan
(WxHxD) [in(mm)]
Technical Data
Max. inverter backfeed current
to the array [A]
27 A rms / 1 cycle,
400 A peak / 0.02 ms
Maximum output overcurrent
protection [A/ P]
40/2
4.4 Battery Input/Output
4.5 Efficiency, Power Consumption and Standard
4.6 Environment Limit
Reverse-Polarity Protection
Model
Battery type
Input/output voltage range [V]
Rated input/output voltage [V]
Maximum input power [W]
Maximum output power [W]
Maximum Input/output current [A]
Li-ion
75-450
150
8094
54
Yes
A-HYB-7.6K-G2
Cycle efficiency charging to
7600
discharging (PCS Only)
92.5%
Internal consumption(night) [W]
Power consumption
Safety
EMC
Certification
RoHS
CEC Weighted Efficiency
97.5%
Model
EVHB-I7
Maximum Inverter Efficiency
98.0%
(PV to GRID)
Standard
FCC part15 class B
IEEE1547, Rule 21,Rule14 (HI)
Yes
Environment limit
EVHB-I7
Storage temperature Range [°F (°C)]
Protection class
Operating Temperature Range [°F (°C)]
De-rating start temperature [°F (°C)]
NEMA 4X
13 to +140 (–25 to +60)
113 (45 ) or above
13 to +167(–25 to +75 )
Overvoltage category
Humidity [%]
Altitude [ft (m)]
Noise emission(typical) [dBA]
0%–95% RH
9843 (3000) MAX
<30
IV (electric supply side), II (PV side)
Topology
Transformerless
Communication
Revenue Grade Data, ANSIC12.20
Warranty [Years]
Rs485, CAN, WiFi (optional) / 4G (optional)
Optional
10
Model
EVHB-I7
Model
EVHB-I7
UL1741,UL1741 SA,UL1699B, CSA C22.2 No. 107.1-16, CSA C22.2 No.292-18
<3W