13
4. Settings for FP7
For connecting GT series and FP7, the communication parameters of FP7 should be set with FPWIN
GR7. Execute "Option" - "FP7 Configuration" menu in FPWIN GR7, and set the parameters in the "Built-
in SCU" page.
Settings
COM0
Set when connecting the COM0 port of FP7 and GT.
COM1 settings
Set when connecting the 1CH of 1-ch or 2-ch type communication cassette
and GT.
COM2 settings
Set when connecting the 2CH of 2-ch type communication cassette and GT.
Communication
mode
Select "MEWTOCOL-7".
Unit number
Set a desired unit number. When using the PLC multiple connection, the unit
number specified by GTWIN corresponds to this unit number.
Baud rate
Set the same "Baud Rate" as that specified in GTWIN "GT Configuration" -
"Communication Parameters" - "Baud Rate".
Data length
Set the same "Data Length" as that specified in GTWIN "GT Configuration" -
"Communication Parameters" - "Data Length".
Parity
Set the same "Parity" as that specified in GTWIN "GT Configuration" -
"Communication Parameters" - "Parity".
Stop bit
Select "1".
RS/CS
Select "Disable".
Send waiting time
For connecting with RS232C or RS422, specify "0".
For connecting with RS485, adjust the setting with the GT and FP7 actually
connected.
Header STX
Select "Disable".
Modem initialization
Select "Not initialize".