5-17
5
E07 Outdoor unit sending failure to indoor unit
Error Detection Method
Error Diagnosis
It is judged an error when a unit itself cannot receive (discrepancy) a signal within a 3-minute period that it had sent.
Outdoor main PC board error
The setting of the terminal resistor select switch on the outdoor main PC board is set incorrectly.
For information on the procedures for replacing the outdoor main PC board, refer to the manual that is packaged with the
service board.
1.
2.
Is the terminal resistor select switch on the outdoor main PC board
set to OPEN?
Is the indoor/outdoor operation line opened or shorted?
1-3
1-4
Replace the outdoor unit main PC board.1-5
Is the indoor/outdoor operation line connected to more than one
outdoor unit? (Network wired?)
1-1
Is the SHORT on the terminal resistor switch on the outdoor main
PC board set to one unit, and the others are OPEN?
1-2
Make the SHORT
setting
1-4
Yes
No
1-2
1-3
Yes
No
1-4
Set the SHORT to
one unit only
Yes
No
1 Outdoor
unit
control
PC board
Correct the wiring
1-5
Yes
No
TERMINAL EEPROM EEPROMTERMINAL
TERMINAL EEPROM TERMINAL EEPROM
A746894 : (U-60PE1R5, U-71PE1R5)
(for single-phase outdoor unit PCB)
A746844 : (U-100PE1R5)
(for single-phase outdoor unit PCB)
A746845 : (U-125PE1R5, U-140PE1R5)
(for single-phase outdoor unit PCB)
A746967 : (U-100PE1R8, U-125PE1R8, U-140PE1R8)
(for 3-phase outdoor unit PCB)
Sec5.indd17Sec5.indd17 2012/03/0920:43:592012/03/0920:43:59