1-21
1
1-4. Operating Range
Temperature Indoor air intake temp. Outdoor air intake temp.
Cooling
Maximum 32°C DB / 25°C WB 46°C DB
Minimum 18°C DB / 14°C WB -15°C DB
Heating
Maximum 30°C DB / − WB 24°C DB/18°C WB
Minimum 16°C DB / − WB -20°C DB / -20°C WB
Sec1.indb21Sec1.indb21 2012/03/0717:29:572012/03/0717:29:57