5-29
5
F08 Outdoor air temperature sensor (TO) trouble
Error Detection Method1.
It is judged an error when open circuit or short circuit.
Error Diagnosis2.
Sensor connector is connected to PC board properly.1-1
1-2
Reconnect and check
Yes
No
1
Sensor
2 PC board
Replace PC board because of outdoor control PC board failure.2-1
Resistance between sockets is infinity or0 ohm.1-2
Replace sensor
2-1
Yes
No