16.1.3 Outdoor Cooling Quiet Operation Control
Purpose
Provide quiet cooling operation when only 1 indoor in operation.
Start Condition
o Indoor fan speed is lower than Lo fan.
o Only 1 operation indoor unit.
o Not in any cooling overload zone.
o Not during annual cooling
o Not initial frequency operation.
o Not during starting control.
o During cool mode
o Not in Heat Recovery mode.
All conditions above are satisfied and function selection enable.
Control Contents
Compressor frequency and outdoor fan speed maximum limit is set. Adjust accordingly.
Cancel Condition
o Indoor fan speed is equal or higher than Lo fan.
o > 1 operation indoor unit.
o In any cooling overload zone.
o During annual cooling
o Initial frequency operation.
o During starting control.
o Not during cool mode
When any above is satisfied