23.2 Error Codes Table
Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify
H00 No abnormality detected
H12 Indoor/Outdoor capacity unmatched 90s after power supply
Total indoor capability more than
maximum limit or less than minimum
limit, or number of indoor unit less than
two.
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
Compressor temperature sensor
(defective or disconnected)
H20 Water pump abnormality Continue for 10 sec.
Indoor PCB
Water pump (malfunction)
H23
Indoor refrigerant liquid temperature
sensor abnormality
Continue for 5 sec.
Refrigerant liquid temperature sensor
(defective or disconnected)
H27 Service valve error Continue for 5 minutes
High pressure sensor (defective or
disconnected)
H28 Abnormal solar sensor Continue for 5 sec.
Solar temperature sensor (defective or
disconnected)
H31 Abnormal swimming pool sensor Continue for 5 sec.
Pool temperature sensor (defective or
disconnected)
H36 Abnormal buffer tank sensor Continue for 5 sec.
Buffer tank sensor (defective or
disconnected)
H38 Brand code not match
When indoor and outdoor
brand code not same
H41 Indoor or Standby Unit Error
3 times occurrence within
40 minutes
Other indoor standby unit error, wrong
wiring & connecting pipe, or expansion
valve leakage
H42 Compressor low pressure abnormality
Outdoor pipe temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compresso
r
H43 Abnormal Zone 1 sensor Continue for 5 sec.
Water temperature Zone 1 sensor
H44 Abnormal Zone 2 sensor Continue for 5 sec.
Water temperature Zone 2 sensor
H51
Outdoor gas pipe temperature sensor
abnormality
Continue for 5 sec.
Outdoor gas pipe sensor (defective or
disconnected)
H53
Outdoor liquid pipe temperature sensor
abnormality
Continue for 5 sec.
Outdoor liquid pipe sensor (defective
or disconnected)
H62 Water flow switch abnormality Continue for 160 sec.
Water flow switch
*H63 Refrigerant low pressure abnormality Continue for 5 sec.
Outdoor low pressure sensor
(defective or disconnected)
H64 Refrigerant high pressure abnormality Continue for 5 sec.
Outdoor high pressure sensor
(defective or disconnected)
*H65 Deice circulation error Continue for 10 sec.
Water flow switch sensor (defective or
disconnected)
Water pump malfunction
Buffer tank (is used)
H67 Abnormal External Thermistor 1 Continue for 5 sec.
Room temperature Zone 1 sensor
H68 Abnormal External Thermistor 2 Continue for 5 sec.
Room temperature Zone 2 sensor
H70 Back-up heater OLP abnormality Continue for 60 sec.
Back-up heater OLP
(Disconnection or activated)
H72 Tank sensor abnormal Continue for 5 sec.
Tank sensor
H74 PCB communication error
Communication or transfer
erro
r
Indoor main PCB and Sub PCB
H75 Low water temperature control
Room heater disable and deice
request to operate under low
wate
r
temperature
Heater operation must enable to
increase water temperature
H76
Indoor - control panel communication
abnormality
Indoor - control panel
(defective or disconnected)
H90 Indoor/outdoor abnormal communication > 1 min after starting operation
Internal/external cable connections
Indoo
r
/Outdoor PCB
H91 Tank heater OLP abnormality Continue for 60 sec.
Tank heater OLP
(Disconnection or activated)