299
29. Technical Data (WH-ADF0309J3E5CM)
29.1 Operation Characteristics
Heating Characteristics at Different Outdoor Air Temperature
Condition
Outdoor air temperature : 7°C (DBT), 6°C (WBT)
Indoor water inlet temperature : 30°C
Indoor water outlet temperature : 35°C
Piping length : 7 m
Outdoor Temperature (°C)
Capacity (kW)
Outdoor Temperature (°C)
Input Power (kW
)
4.700
5.400
6.100
6.800
7.500
8.200
-15-14-13-12-11-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12
1.400
1.600
1.800
2.000
2.200
2.400
-15-14-13-12-11-10-9-8-7-6-5-4-3-2-10123456789101112
29.2 Heating Capacity Table
Water Out (°C) 25 35 45 55
Outdoor Air (°C)
Capacity
(W)
Input Power
(W)
Capacity
(W)
Input Power
(W)
Capacity
(W)
Input Power
(W)
Capacity
(W)
Input Power
(W)
-15 4850 2150 4750 2280 4650 2440 4500 3200
-7 5400 1700 5600 1970 5600 2400 5300 2780
2 6500 1770 6700 2060 6600 2450 6000 2890
7 8160 1630 8000 1900 8000 2300 8000 2850
12 8220 1280 8000 1520 8000 2000 8000 2600

Table of Contents