Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify
H95 Indoor/Outdoor wrong connection
Indoor/Outdoor supply voltage
H98 / F95
Outdoor high pressure overload
protection
Cooling high pressure overload
protection
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Room Air Filter dirty or air circulation
short circuit
H99 Indoor heat exchanger freeze prevention
Indoor heat exchanger
Refrigerant shortage
F12 Pressure switch activate
4 times occurrence within
30 minutes
Pressure switch
F14 Outdoor compressor abnormal revolution
4 times occurrence within
20 minutes
Power transistor module faulty or
compressor lock
F15 Outdoor fan motor lock abnormality
2 times occurrence within
30 minutes
Outdoor fan motor lead wire &
connector
Fan motor lock or block
F16 Total running current protection
3 times occurrence within
20 minutes
Excess refrigerant
Outdoor PCB
F20
Outdoor compressor overheating
protection
3 times occurrence within
30 minutes
Compressor tank temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compresso
r
F22
IPM (power transistor) overheating
protection
4 times occurrence within
30 minutes
Improper heat exchange
IPM (Power transistor)
F23
Outdoor Direct Current (DC) peak
detection
7 times occurrence
continuously
Outdoor PCB
Compresso
r
F24 Refrigeration cycle abnormality
4 times occurrence within
60 minutes
Insufficient refrigerant
Outdoor PCB
Valve Close
F25
Cooling/Heating cycle changeover
abnormality
4 times occurrence within
30 minutes
4-way valve
V-coil
F27 Pressure switch abnormality Continue for 1 min.
Pressure switch
*F29 Low Discharge Superheat
1 times occurrence within
2550 minutes
Discharge Temperature Sensor
Discharge Pressure Sensor
Pressure Switch
Outdoor PCB
F30 Water outlet sensor 2 abnormality Continue for 5 sec.
Water outlet sensor 2 (defective or
disconnected)
F32 Abnormal Internal Thermostat Continue for 5 sec.
Control panel PCB thermostat
F33 Freezing of standby unit error
3 times occurrence within
40 minutes
Wrong wiring and connecting pipe, or
Expansion valve leakage
F36
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
Outdoor air temperature sensor
(defective or disconnected)
F37
Indoor water inlet temperature sensor
abnormality
Continue for 5 sec.
Water inlet temperature sensor
(defective or disconnected)
F40
Outdoor discharge pipe temperature
sensor abnormality
Continue for 5 sec.
Outdoor discharge pipe temperature
sensor (defective or disconnected)
F41 PFC control
4 times occurrence within
20 minutes
Outdoor PCB
F42
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
Outdoor heat exchanger temperature
sensor (defective or disconnected)
F43 Outdoor defrost sensor abnormality Continue for 5 sec.
Outdoor defrost sensor (defective or
disconnected)
F45
Indoor water outlet temperature sensor
abnormality
Continue for 5 sec.
Water outlet temperature sensor
(defective or disconnected)
F46
Outdoor Current Transformer open
circuit
Insufficient refrigerant
Outdoor PCB
Compressor low
*F48
Outdoor EVA outlet temperature sensor
abnormality
Continue for 5 sec.
Outdoor EVA outlet temperature sensor
(defective or disconnected)
*F49
Outdoor bypass outlet temperature
sensor abnormality
Continue for 5 sec.
Outdoor bypass outlet temperature
senso
r
(defective or disconnected)
Note: * This error code is not applicable for this system.