245
Diagnosis
display
(Indoor
model:
CS-XX /
S-XX /
WH-XX)
Abnormality
or
protection
control
LED
6
LED
5
LED
4
LED
3
LED
2
LED
1
A
bnormality
judgement
Protection
operation
Problem Check location
H36 / F23 /
H51
Outdoor gas pipe
temperature
sensor
abnormality
Continuous
for 5s
Heating
protection
operation
only
Outdoor gas pipe
temperature
sensor open or
short circuit
Outdoor gas
pipe
temperature
sensor lead wire
and connecto
r
H37 / F24 /
H53
Outdoor liquid
pipe temperature
sensor
abnormality
Continuous
for 5s
Cooling
protection
operation
only
Outdoor liquid
pipe temperature
sensor open or
short circuit
Outdoor liquid
pipe
temperature
sensor lead wire
and connecto
r
H64 / P04 /
F27
Outdoor high
pressure sensor
abnormality
Continuous
for 1
minute
- High pressure
sensor open
circuit during
compressor stop
High pressure
sensor
Lead wire and
connecto
r
H89 / F16 /
H64
Compressor
discharge
temperature
sensor
abnormality
4 times
happens
within 20
minutes
- High pressure
sensor open or
short circuit
High pressure
sensor
Lead wire and
connector
H97 / P22 /
F15
Outdoor fan motor
mechanism lock
2 times
happen
within 30
minutes
- Outdoor fan motor
lock or feedback
abnormal
Outdoor fan
motor lead wire
and connector
Fan motor lock
or block
H98 / - /
H98
Indoor high
pressure
protection
- - Indoor high
pressure
protection
(Heating)
Check indoor
heat exchanger
Air filter dirty
Air circulation
short circuit
H99 / - /
H99
Indoor operating
unit freeze
protection
- - Indoor freeze
protection
(Cooling)
Check indoor
heat exchanger
Air filter dirty
Air circulation
short circuit
H64 Outdoor high
pressure switch
abnormality
- - High pressure
switch open circuit
during
compressor stop
High pressure
switch lead wire,
connector
CN-PSW1
H89 High pressure
sensor abnormal
- - High pressure
sensor open or
short circuit
High pressure
sensor lead
wire, connector
CN-HPS
F11 / L18 /
F25
4-way valve
switching
abnormality
4 times
happen
within 30
minutes
- 4-way valve
switching
abnormal
4-way valve
Lead wire and
connector.
F17 / P14 /
F33
Indoor standby
units freezing
abnormality
3 times
happen
within 40
minutes
- Wrong wiring and
connecting pipe,
expansion valve
leakage.
Check
indoor/outdoor
connection wire
and pipe
Indoor heat
exchanger
sensor lead wire
and connector
Expansion valve
lead wire and
connector.
F90 / H02 /
F41
Power factor
correction (PFC)
circuit protection
4 times
happen
within 20
minutes
- Power factor
correction circuit
abnormal
Outdoor PCB
faulty
F91 / P15 /
F24
Refrigeration
cycle abnormality
4 times
happen
within 60
minutes
- Refrigeration
cycle abnormal
Insufficient
refrigerant or
valve close