25.2.9 Abnormal Zone 1 Sensor (- / - / H43)
Malfunction Caused:
1 Faulty connector connection.
2 Faulty buffer tank sensor.
3 Faulty indoor sub PCB.
Abnormality Judgment:
Continue for 5 seconds.
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
NO
YES
YES
Check plug out connector from zone 1 connector sub PCB in
match?
the PCB measure resistance of zone 1 sensor characteristic
Abnormal zone 1 sensor
Check the turn off power check connector connection
Normal?
Poor contact
Correct connection
NO
Defective zone sensor
Defective zone sensor
Replace sensor
Defective PCB
Replace PCB