45
10-2.
Operating the High-spec Wired Remote Controller (CZ-RTC5B)
20:30 (THU)
START
[ ]
How to set the external static pressure
1. Keep pressing the
, and buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
20:30 (THU)
2. Press the or button to see each menu.
If you wish to see the next screen instantly, press the
or button.
Select “8. Detailed settings” on the LCD display and press
the button.
The “Detailed settings” screen appears on the LCD display.
3. Select the “Unit no.” by pressing the or button
for changes.
4.
Select the “Code no.” by pressing the or button.
Change the “Code no.” to “B0” by pressing the or
button (or keeping it pressed).
5. Select the “Set data” by pressing the
or button.
Select one of the “Set data” among “0001” – “0010”
according to the desired external static pressure setting by
pressing the or button.
Then press the button.
(See Table 10-2.)
When setting to auto airflow volume control:
Select the setting data to “-002”.
Then press the
button.
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel. Page [ ] Confirm
7. Simple settings
Detailed settings
Unit no. Code no. Set data
10
1-1 0005
20:30 (THU)
Detailed settings
Unit no. Code no. Set data
1-1
-001
Sel. Next
20:30 (THU)
B0
Detailed settings
Unit no. Code no. Set data
1-1
Sel.
20:30 (THU)
B0 0001
[ ] Confirm
Detailed settings
Unit no. Code no. Set data
1-1
Sel.
20:30 (THU)
B0 -002
[ ] Confirm
01_350221_Eng.indb 45 2023/3/17 10:01:16