77 
12.11 Sterilization Mode 
 Purpose: 
o  To sterilize water tank by setting the required boiling temperature. 
 
  Control start condition: 
o  Tank connection menu is set to YES by control panel. 
o  Sterilization menu is set to YES by control panel. 
o  Sterilization signal received from control panel by timer. 
 
 Control stop condition: 
o  After sterilization timer completed or 
o  After 4 hours of operation since sterilization function starts. 
 
 Control content: 
o  Once the sterilization function is enable, set the target sterilization set temperature. 
o  Booster heater will allow to ON during solar SET condition. 
  Booster heater OFF Temp = Sterilization set temperature +0°C 
  Booster heater ON Temp = Sterilization set temperature -7°C 
o  Sterilization timer which set by control panel will start count after tank achieve sterilization set temperature. 
o  Target tank temperature will set back to normal tank set temperature. 
 
* Tank heater control is not affected by solar pump when solar priority set. 
12.12 Quiet Operation 
 Purpose: 
o  To provide quiet operation compare to normal operation by reduces outdoor unit noise.  
 
 Starting condition: 
o  When quiet button is presses. 
o  When quiet is request to ON by weekly timer. (Refer to control panel) 
 
  When any of above mentioned condition is achieved, this control is activated. 
New target FM speed = Present target FM speed – 80 rpm 
Minimum target FM speed = 200 rpm 
 
 Cancellation condition: 
o  Cancel by pressing quiet button. 
o  Stop by OFF/ON button 
o  When quiet is request to OFF by weekly timer.