89 
13.2  Protection Control for Heating Operation 
13.2.1  Outdoor Air Temperature Control 
The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid 
compressor overloading. 
13.2.2 Deice Operation 
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor 
stop. 
 
  Deice judging condition 
 
-30
-30 -20 -10 0 10 20 30
-25
-20
-15
-10
-5
0
5
10
OD Pipe Temperature (°C)
Outdoor Unit Deice Control
line for continuous 3 minutes
and Pipe Temperature below this
When Heating Time > 35 minutes
Outdoor Temperature (°C)
3. Heating accumulation time
1. Outdoor air sensor temp.
2. Outdoor pipe sensor temp.
Deice start depends:
 
 
  Deice mode selection condition 
o  There are 2 deice modes, according to water inlet temperature and outdoor ambient temperature the deice 
mode is decided. 
 
50°C
27°C
-
10°C
Water inlet temperature
Outdoor ambient temperature
Deice mode 1
Deice mode 2
 
 
Judgement details: 
1)  When water inlet temperature is more than 50°C, unit will operate deice mode 1. 
2)  When water inlet temperature is less than 27°C, unit will operate deice mode 2. 
3)  When water inlet temperature is less than 50°C and outdoor ambient temperature is less than -10°C, unit will 
operate deice mode 2. 
4)  When water outlet temperature sensor 2 detect temperature is less than 22°C, unit will operate deice mode 2.