Panasonic WH-SXC12H9E8 - Installer System Setup: Bivalent Control Logic; Advanced Parallel Heat Control Parameters; Advanced Parallel DHW Control Parameters

Panasonic WH-SXC12H9E8
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
Menu Default Setting Setting Options / Display
Control pattern Advanced parallel
Heat Selection of the tank
“Heat” implies Buffer Tank and “DHW” implies
Domestic Hot Water Tank.
Control pattern
Advanced parallel Heat Yes
Buffer Tank is activated only after selecting
“Yes”.
-8 °C
Set the temperature
threshold to start the
bivalent heat source.
0:30
Delay timer to start the
bivalent heat source
(in hour and minutes).
-2 °C
Set the temperature
threshold to stop the
bivalent heat source.
0:30
Delay timer to stop the
bivalent heat source
(in hour and minutes).
Control pattern Advanced parallel DHW Yes
DHW Tank is activated only after selecting
“Yes”.
0:30
Delay timer to start the
bivalent heat source
(in hour and minutes).