023-064X Technical Manual
4
1.4 Specifications
Supply 24 vac 50/60 hz (17-28 vac) 0.21 amps, 5 va
Relay SPDT, 5 amp
@
125 vac,
non-inductive
On delay; 0-999 seconds (16 minutes) Off delay; 0-999 seconds (16 minutes)
2 analog output 4-20 ma or 2-10v jumper configurable
Operating temperature -20 ºC to 40 ºC (-4 ºF to 104 ºF) -40 ° under some conditions
For indoor use
Flame resistant Polycarbonate ABS enclosure rated UL94-V0, 5VB, and 5VA
Standards. Conforms to UL61010-1, CSA C22.2
61010-1-12, ANSI/ISA 61010-1, CSA C22.2 no. 205-12
Pollution degree 2
Installation category II
Altitude 2000
m (6500 ft)
Humidity max 80% rh. 80% to temperatures up to 31 ºC (88 ºF),
decreasing linearity to 50% rh at 40 ºC (104 ºF)
1.5 User Interface:
Back lit LCD display shows gas concentration, user settings and alarm status
Red LED alarm indicators, gas level 1 and 2
High intensity white LED strobe on level 3
Audible alarm, 85 db at 1 meter (3.3 ft)
4 pushbutton  user keypad
Password control for
settings
1.6 Gas sensor spec:
Sample frequency, continuous, maximum 1 second
Response time to gas is less than 30 seconds to 90% reading
Type of sensing element is electro-chemical for toxic gases, semiconductor for refrigerants
Coverage is maximum 50 feet each side of sensor with no obstructions
Sensor Memory Module type of gas, scale, sensor calibration points, zero, gain
Front
Side
Back
Top
7.7 in
19 cm
4.8 in
12 cm
1.9 in
5 cm
5.5 in
14 cm
1.5 in
4 cm
Snap in feet
for mounting
on columns
7/8 in
2.2 cm