023-064X Technical Manual
8
3.2 User settings list
To view the current settings on the model 023-064X, press right several times.
To modify the current setting press up or down .
To save, press left and up arrows and at the same time. The appearance of **OK** will confirm successful
save.
Setting Code Definition Display Maximum value default
=============================================================================
Sensor A (first module, plugged into the top slot) Firmware rev 2B29.9
Sensor B (second module, plugged into the bottom slot)
00 18 Alarm 1 and relay limit AL1 sensor scale 400ppm
01 19 Alarm 1 set time (seconds) A1Del 999 5s
02 20 Alarm 1 reset time (seconds) A1Off 999 300s
03 21 Alarm 2 limit AL2 sensor scale 400ppm
04 22 Alarm 2 set time A2Del 999 5s
05 23 Alarm 2 reset time A2Off 999 300s
06 24 Alarm 3 limit AL3 sensor scale 400ppm
07 25 Alarm 3 set time A3Del 999 5s
08 26 Alarm 3 reset time A3Off 999 5s
40 sensor A analog output zero (factory set) AnZA 255
41 sensor A analog output span (factory set) AnSA 255
42 sensor B analog output zero (factory set) AnZB 255
43 sensor B analog output span (factory set) AnSB 255
44 °C temperature display 0=off 1=on Temp 0/1 0
45 audio alarm 3 off/on Aud 0/1 1
49 Keyboard security lock, 0=off, 1=on KBL 0/1 0
50 Temperature modify/correct TMod -9/+9°C
51 High temperature alarm limit (alarm 1) ATHi 0-99°C 60
52 Warm up delay, disables alarms on power up W/U 0-99 mins 60
55 Low temperature alarm limit (alarm 3) ATLo 0-99°C 0
56 Network Display on/off (non BACnet version) Net 0/1 0
57 sensor A refrigerant ppm scale Ref-A Refrig list Rx
58 sensor B refrigerant ppm scale Ref-B Refrig list Rx
Where default Rx is R507 for 023-0642 and R22 for 023-0643
3.3 Test
Analog output
To test the output signal, power the sensor and wait for the warm-up period to expire
Press right several times until you see 40 AnZA. Press up or down to fine tune the output.
Use 40 AnZA to force sensor A output to 2V (4mA) (min range 0 ppm)
Use 41 AnSA to force sensor A output to 10V (20mA) (max range)
Use 42 AnZB to force sensor B output to 2V (4mA) (min range 0 ppm)
Use 43 AnSB to force sensor B output to 10V (20mA) (max range)
Relay output
To force the relay output 1 for 5 minutes, press up for more than 5 sec. Add 5 minutes each time you
press up .
“MAN” or “M” at the left of the display will tell that the relay is overridden.
To cancel the relay override, press down .