023-064X Technical Manual 
 
 
10 
6  MT Alliance installation  
 
Log into MT Alliance. You must have technician refrigeration configuration permissions.  
Enter configuration Mode. 
Select and zoom in the view where the sensor is located. 
From the Components box Pick and drop a Sensor 
 
Then select Absolute Gas Concentration Type, Local Source, Micro Thermo Manufacturer and the 
Sensor Model and gas type you are going to monitor (pre-defined sensor model will be available in 
version MTA 8.5. For previous version create a user defined model at the next section or use the 023-
034X series) 
 
 
 
Click OK then click on the new button.  
 
 
Select the Detail tab and enter a sensor name in the Identification field and put “Normal reading is 
less than 10 ppm when no gas is present” in the Notes field (put 2 ppm more than 1% of full range)