023-064X Technical Manual 
 
 
70-PHW-1018-R3.2 MTA 8.5 023-064X Refrigerant Leak Detector Manual.docx  5 
 
2  Installation 
Important. All wiring must conform to local building codes, regulations and laws. If the equipment is used in 
a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. 
2.1  Sensor Placement 
 
Coverage 
Guidelines for sensor placement of diffusion type sensors are based on the reasonable delay for gas to 
get from the source 
to 
the sensor.  All sensors are created equal in this r
egar
d.
 
•  For air quality control of exhaust emissions and accumulations of toxic gases the generally 
acceptable 
maximum radius of coverage is 50 feet (15 meters). Approximately 7500 square 
feet (700 square meters). 
• 
For leak detection of combustible gases, ammonia, refrigeration gases the maximum radius is 30 
feet (10
 meters) since they can escape more quickly and the risk is greater. 
The radius of coverage of any sensor does not extend 
beyond 
any obstruction that impedes natural 
circulation of air.  This includes walls, stairs, elevators, shelving with solid fill, 
tool 
chests, etc.  The 
sensor must “see” the area of coverage; if 
not, 
another 
sensor(s) 
is required. 
 
Mounting Heights 
Mounting heights for gas sensors are based on their density, relative to air.  There are three 
groups;
 
1.  A gas lighter than air will be more concentrated near the ceiling; hydrogen, methane (natural 
gas), ammonia, helium. Install at 1 to 3 feet from ceiling. 
2.  A gas similar density to air will be diluted in air equally at all levels; - carbon monoxide, nitrogen 
dioxide, hydrogen sulfide, oxygen, carbon dioxide.  Install from 3 feet 
(1 
meter)
 off floor to one half 
of the ceiling height.  For vehicle emissions carbon monoxide detectors combined 
with 
nitrogen 
dioxide detectors are installed at 3 to 5 feet (1 to 2 meters) from the floor when the ceiling is 7 to 10 
feet high.  If the ceiling height is higher than 10 feet, for example for heavy equipment, the carbon 
monoxide detectors are installed at 3 to 5 feet (1 to 1.5 meters) from the floor as per the 
requirements of the Canada building code and the nitrogen dioxide detectors should be installed at 
50% of the ceiling height and above the vehicle height.  If the exhaust pipes of diesel vehicles are 
below the vehicles, then the nitrogen dioxide detectors should be installed at 3 to 5 feet (1 to 1.5 
meters) from the floor.  In all cases the 
detectors 
must be installed above obstructions blocking 
circulation 
of 
air in front of the detectors; example, maintenance garages in automobile dealerships 
where tool chests, work tables and storage racks typically line all walls. 
3.  A gas heavier than air will concentrate near the floor; - HFCs, HCFCs, propane, chlorine, most 
organic vapors, butane.  Install 1-3 feet (30cm to 1 meter) from floor. 
 
For all types of sensors avoid drafts, obstacles, aerosols, silicones. Place sensors in the center of its 
coverage area as much as possible. 
 
2.2  Maintenance guide 
Visual verification recommended frequency: once per week.  The system incorporates monitoring software 
which checks the operation of the circuits.  This software is always running when the unit is powered on.  Ensure 
that the unit is installed on an independent circuit.  It is recommended that the unit be checked once per week to 
ensure that it is on, by the presence of reading on the display.  
Verification of communication and calibration of sensors recommended frequency: once per year.  It is 
recommended that sensor be verified with standardized bottled gas mixtures by the manufacturer or other 
qualified specialist or the sensor plug-in module be replaced with a new or factory calibrated module.   The 
communication between the sensor and control systems should be tested.  A report of compliance should be 
supplied and available on the site.