22
Parker Hannifin Manufacturing Germany GmbH & Co. KG
Pump & Motor Division Europe
Chemnitz, Germany
Electro hydraulic proportional controls version 45 for
axial piston pumps, PV series
Bulletin MSG30-3254-INST/UK
Installation and setup manual
12. Cables and connections
Cable 1 from CIP and LVDT (displacement transducer)
Cable 2 from pressure sensor (compensator codes ...UPM, …UPF, ...UPQ)
cable:3 x 0,5 mm², shielded, max. 50 m long
connector: according DIN 43 650, version AF, 4-pin
protection class IP 65 for voltages up to 250
Alternative: shielded cable with molded
connector; in dierent length and variations.
cable: 4 x 0,5 mm², shielded, max. 50 m long
connector: CIP: round type M12 x 1; 4-pin
LVDT: round type M12 x 1; 5-pin
angled version
protection class IP 65 for
voltages up to 250 V
CIP
PQ-module, control
Pin 6
+24 V
Teach-in
Pin 9
PQ-module, control
LVDT
cable 3 a/b: 3 x 0,5 mm², shielded, max. 50 m long
connector: according DIN 43 650, version AF, 4-PIN
protection class IP 65 for voltages up to 250V
cable: 4 x 0,5 mm², shielded, max. 50 m long
connector: CIP: round type M12 x 1; 4-pin
LVDT: round type M12 x 1; 5-pin
angled version
protection class IP 65 for voltages uop to 250 V
Notice: To protect the sensor, a cable strain
relief should be provided on the system side.