3
(Refer to Temperature Limits)
Size
Orifice
Act. Bench
Reverse Shutoff*
Bench
Direct Shutoff*
(inches) Size Range 3-15 psi 0-20 psi
0-30 psi
Range 3-15 psi 0-20 psi
0-30 psi
1/2 A, C, E 36 6-15 0-400 3-12 0-400
B 36 6-15 0-400 3-12 0-300
————3-9301-400
T 36 6-15 0-300 3-9 0-400
3/4 T 36 6-15 0-100 3-9 0-250
9-15 101-225
12-15 226-300
60 12-15 0-400 3-7 0-400
1 T 36 9-15 0-150 3-9 0-100
12-15 151-250
13-15 251-400
60————3-70-400
1-1/4 T 36 9-15 0-150 3-9 0-150
12-15 151-200
13-15 201-250
60 12-15 0-300 3-7 0-300
13-15 301-400
1-1/2 T 36 12-15 0-150 —-
13-15 151-200
60 12-15 0-225 3-7 0-200
13-15 226-275
2 T 36 12-15 0-50
13-15 51-75
60 12-15 0-125 3-7 0-100
13-15 126-175
2-1/2 T 60 10-15 0-75 0-100 0-100 3-8 0-70 0-110 0-200
12-15 76-125 101-125101-125 3-8 0-70 0-110 0-200
22-30 125 125 3-8 0-70 0-110 0-200
3 T 60 10-15 0-40 0-60 0-60 3-8 0-40 0-60 0-100
12-15 41-60 0-80 0-80 3-8 0-40 0-60 0-100
22-30 81-110 81-110 3-8 0-40 0-60 0-100
4 T 60 12-15 0-20 0-32 0-32 3-8 0-10 0-15 0-25
22-30 33-50 33-50 3-8 0-10 0-15 0-25
* Shutoff pressures are in conformance with ANSI/FCI 70-2 Class IV
CAUTION: K1 designed for 3-15 psi. Do not exceed 20 psi.
Reverse Acting - Fail Closed/Air to Open (FC/ATO)
Direct Acting - Fail Open/Air to Close (FO/ATC)
† Based on 20 psi air supply with positioner.
‡ Based on 30 psi air supply.
K1 & K4 ACTUATOR SHUTOFF TABLE
PRODUCT IDENTIFICATION
MODEL NUMBER ORIFICE SIZE CONNECTIONS TRIM PACKING
ACTUATOR SPRING
(Must be 2 Digits) (Must be 2 Digits) (Must be 2 Digits)
example: K
1 T E 8 1 1 —36 R B
K1 - Bronze, Pneumatic A C -
1
2 2 - 125 Flg 1 - Metal 1 - V-ring K1 & K4 only K1, K5, K6 only K4 only
K4 - Cast Iron, Pneumatic B D -
3
4 8 - Unions 01 - None DA - 3-12 Dir 36 DH - 3 - 8 Dir 60
K5 - Bronze, Electric, FC C E - 1 36 – 36 in
2
DB - 3-9 Dir 36 RH - 10-15 Rev 60
K6 - Bronze, Electric, FO E F - 1
1
4 60 – 60 in
2
RA - 6-15 Rev 36 RQ - 12-15 Rev 60
T G - 1
1
2 RB - 9-15 Rev 36 RT - 22-30 Rev 60
H - 2" K5 & K6 only RC - 12-15 Rev 36
J - 2
1
2 90 - 0-10vDC RD - 13-15 Rev 36
K - 3 91 - 4-20mA DF - 3-10 Dir 60
M - 4 92 - 0-135 ohm DG - 3-7 Dir 60
RG - 12-15 Rev 60
RH - 13-15 Rev 60
01 - None (K5, K6 only)
KOMBAT SERIES K VALVE ORDERING CODE
POSITIONER POSIT. SET ACCESSORIES
(Must be 2 Digits) (Must be 2 Digits) (Must be 2 Digits)
M
P 0 2 0 1
For use with K4 Valves Only
A - None 01 - None 01 - None
MI - Moore I/P 02 - 3-15/4-20 mA 02 - Limit Switch, Mechanical
MP - Moore P 03 - 3-9/4-12 mA 03 - Limit Switch, Proximity Sw.
4P - PMV P4 P 04 - 9-15/12-20 mA 04 - Feedback Potentiometer 1K
5I - PMV P5 I/P 05 - Feedback 4-20mA Posit. Tra
5P - PMV P5 P