Use a nqinimum 2-1/2" foot piece of 3" diameter
AL29 4C stainless steel vent pipe fol insertion
through Wall Thimble. See Vvnt Pipe section below
for vent pipe requirements
Slide Stainless Steei Collar over vent pipe and slide
3" diameter hose clamp and collar to vent pipe
Insert pipe with collar through Outside Vent Cap and
slide 3" diameter hose clamp and collar to vent pipe.
Leave at least 2" of vent pipe protruding beyond
face of Vent Cap and secure hose clamp and collar
to vent pipe.
Place Outside Vent Cap over Wall Thimble with air
openings in Vent Cap facing down. Secure Cap to
Thimble with #10 sheet metal screws
9. Place 3' diameter hose clamp over pipe protruding
through inside of Wall Thimble
10. Place Inside Thimble Cap and Collar onto Wall
Thimble. Access hose clamp through 4" diameter
collar on bottom of Thimble and secure hose clamp
over collar and vent pipe as per step 7 above.
1 1 Secure Inside Thimble cap to Wall Thimble with # 10
screws Seal Thimble Cap perimeter with silicone
12 Seal all openings between Wall and Thimble and
around the 3- diameter stainless steel vent pipe that
protrudes through hlside and outside of Wall
Thimble
13 Add any bracing that may be needed to support Wall
Thimble on inside of wall structure.
14, Secure Outside Vent Cap to exterior wall with four
#]0 sheet metal screws provided.
15 Attach Z-Flex #2SVSTPF03 terminal to protruding
vent pipe Refer to Figure 9. To attach to HEATFAB
pipe. insert into pipe end and fold over tabs to
secure Otherwise, silicone terminal to vent pipe.
VENT PIPE MALE END
(SEAL VENT _///
FOLLOWING VENT PEERLESS// /
MANUFACTURER'S WALL THIMBLE /, r_/
INSTRUCTIONS) _ _/
\
VEN
OR
_. TO 4" DIA I_j
FAN ADAPTER f SILICONE AIR BOX
CONNECTION _//'
/
OUTSIDE
2 _ MIN
f SILICONE
02-SVSTPXOS
AIR iNLET TERMIN ATION
OPENINGS
_EXTERIOR WALL
,,' 11
L
ALTERNATE LEFT /SIDE AIR BOX
CONNECTION
_- BOILER
--4" DIA AIR 80X
CONNECTION
Figure 9: Side Wall Venting System
9