1. PREINSTALLATION
Read carefully study th_se instructions before beginning \vork
This boiler must be installed by a qualified contractor
The boiler warranty can be voided if the boiler is not instal}ed, maintained and serviced correctly.
The equipment must be installed in accordance with those installation requirements of the authority having
jurisdiction or, in the absence of such requirements, to the current edition of the National Fuel Gas Code, ANSI
Z223. f/NFPA 54.
Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
Install boiler not less than 24" between the left side, top.
and front of the boiler and adjacent wall or other
appliance, when access is required for servicing.
The design of this boiler is certified for closet installation
with the following clearances:
1. 6" between right side, front and combustible
cotlstruction
2. ]2" between top of jacket and combustible
construction
3. 1"" between left side, rear and combustible
construction,
4. 2" between vent pipe and combustible construction.
5. 0" between wall thimble and combustible
construction
6. This boiler is design certified for use on combustible
flooring
K4 ! [ollJ _ dI _ m]'] :3 i -"{o]! :ill _Vllll_[ยข'F;_
The following LP requirements from the Uniform
Mechanical Code, section 304.6, may be in effect in
your geographic area:
"Liquefied petToleum gas-burning appliances shall
not be installed in a pit. basement or similar location
where heavier-than air gas might collect. Appliances
so fueled shall not be installed in an above-grade
under-floor space or basement unless such location
is provided with an approved means for removal of
unburned gas."
D]q I h__.'t If_,1II If_*_lII [*] _,_H-'l IJ ;iLv__i"
For new and existing installations, a Water Installation
Survey is available from Peerless Heater Company. The
survey will provide information on how a hot water
boiler works with your specific system and will provide
an overview of hot water system operation in general.
You can also use this survey to locate system problems
which will have to be corrected. To obtain copies of the
Water Installation Survey, contact your Peerless
representative.
I=m I:Jar,..1b,'_h,'llh.'_[_ili:l:l IIr_,V='ollj
Do not install this boiler on carpeting. Boiler
installation on carpeting is a fire hazard. Install this
boiler on non-combustible flooring or use a
combustible floor pan to install this boiler on other
non-carpeted flooring.
Prepare sketches and notes of the layout to minimize the
possibility of interferences with new or existing
equipment, piping, venting and wiring. Review
Limitations on vent pipe, vent terminal, and air inlet pipe
locations and ventilation air requirements in Section 4.
Liquefied Petroleum (LP) is heavier than air and may
collect or "pool" in a low area in the event of a leak
from defective equipment. This gas may then ignite,
resulting in a fire or explosion. See the instructions
below.