EasyManua.ls Logo

PEERLESS SERIES PSC - Page 26

PEERLESS SERIES PSC
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 6: Meter Conversion - Natural Gas
Burner inputs in Btu/hr for various meter timings and
heat values (Tables based on 2 cubic feet of gas through
meter)
Time that Heat Value of Gas
meter is (Btu/cubic
read (sec)
25
30
35
40
45
50
55
60
65
70
75
8O
85
90
95
i00
I05
110
115
120
125
foot)
1000 1025
288000 295200
240000 246000
205714 210857
180000 184500
160000 164000
144000 147600
130909 134182
120000 123000
110769 113538
102857 105429
96000 98400
90000 92250
84706 86824
80000 82000
75789 77684
72000 73800
68571 70286
65455 67091
62609 64174
60000 61500
57600 59040
1050
302400
252000
216000
189000
168000
151200
137455
126000
116308
108000
100800
94500
88941
84000
79579
75600
72000
68727
65739
63000
60480
I_ll [_l:l_[_l[_01111111".l;{0I_l_lDlll;t
1. After starting the boiler, be certain all controls are
working properly. Check to be sure that the limit will
shut off the boiler in the event of excessive water
temperature, This can be done by lowering the limit
setting until the main burners shut down. When
proper limit function is confirmed, return the dial to
its previous setting.
2. To check operation of the ignition system safety
shut-off features:
a, Turn gas supply off.
b. Set thermostat or controller above room
temperature to call for heat. Watch for igniter
glow at pilot burner.
c Igniter will continue to glow for 30 seconds, de
energize for 30 seconds, then re energize and
glow for another 30 seconds. It will then de
energize for 5 minutes before restarting the
sequence
d Turn gas supply on
e. Reset the boiler and control by following
Operating Instructions.
f Observe boiler operation through one complete
cycle.
3.
4.
5.
6.
7.
8.
Low Water Cut Off (if used) Consult the
manufacturer's instructions for the low water cut-off
operational check procedure.
Check the system to make sure there are no leaks or
overfilling problems which might cause excessive
make-up water to be added. Make-up water causes
liming in the boiler and brings in oxygen. Oxygen
can cause severe damage to the boiler though
oxygen corrosion pitting.
Check the expansion tank and automatic fill valve (if
used) to confirm that they are operating correctly. If
either of these components causes high pressure in
the system, the boiler relief valve will weep or open,
allowing fresh water to enter the system.
Do not allow the system controls to subject the boiler
to excessively low water temperatures, which would
cause condensation of flue gases and corrosion of
the boiler. Operate the boiler at a temperature above
130°F. Adjust the boiler limit as required to maintain
boiler temperature above this level.
Check the general condition of the system including
piping support, joints, etc. Check cleanliness of the
radiators, baseboard units and/or convectors. Clean
them to the extent possible. If radiators do not heat
evenly, vent any remaining air from them.
Review operation and User's Information Manual
with end-user.
9.
10.
Complete the Warranty Card and submit it to
Peerless Heater Company.
Hang the Installation, Operation and Maintenance
Manual, User's Information Manual, and Vent
Manufacturer's Information Manual in an accessible
position near the boiler.
23

Related product manuals