E. USER MENU
The User menu is accessible from the default screen by
pressing the M button once to enter the menu level
selection screen and pressing M again when “0000” is
shown in the small digits.
The User Menus allow access to basic setpoints, system
test, and unit settings. Use buttons R1 and R2 to move
between parameters.
F. STATUS MENU
–
1000 LEVEL
The Status Menu is accessible from the default screen by
pressing the M button once to enter the menu level
selection screen. Using R1 and R2, select “1000” in the
small digit area. Press M to enter the Status Menu.
The Status Menu allows for in-depth boiler information to
be viewed but cannot access parameters for modification.
33
BOILER CONTROL: INTERNAL WIRING & OPERATION
Table 8.5: User Menus (0000 Level)
User
(0000)
Parameters
Parameter Function
Units/Options
0003
–
CH Setpoint, CH enable/disable
Temperature
0048
–
DHW Setpoint, DHW enable/disable
Temperature
0200
–
10 minute System Test. Once 10 minute timer is over boiler
will return to normal state.
–
Additional Access with Installer access PIN
–
Input installer PIN using CODE menu then return to User
Menu for advanced system test functions.
–
OFF
-
System Test Disabled
–
FAN
-
Test blower (fixed speed)
–
Lo
-
Test burner at low power
–
Ign
-
Test burner at igniton power
–
Hi
-
Test burner on high power
–
REg
-
Test burner at high power with supply setpoint enabled
Installer level only:
–
Stb
-
Test maximal thermostat
–
LCO1
-
Test Low Water Cut-off 1
0901
–
Temperature unit setting °C/°F
0902
–
Pressure unit setting Bar/psi
0997
–
Screen Test
– Pressing select activates all LCD options
No options
Table 8.6: Status Menus (1000 Level)
Status
(1000)
Parameters
Parameter Function
Value/Options
1001
Supply temperature Temperature
1002
DHW temperature Temperature
1004
Outside temperature Temperature
1005
2nd Supply temperature Temperature
1006
Flue temperature Temperature
1007
Return temperature Temperature
1008
Ionization / flame current µA
1010
CH Pump On/Off
1012
Actual CH setpoint Temperature
1013
Room Thermostat (RT) input Open/Closed