K-System – Isolated Barriers
Dismounting, Maintenance, and Repair
6 Dismounting, Maintenance, and Repair
Disconnecting Circuits
1.
Disconnect the power supply.
2. Disconnect the field circuit.
3. Disconnect the control circuit.
4. Disconnect the HART communication, if available.
Danger!
Explosion hazard from live wiring of non-intrinsically safe circuits
If you connect or disconnect energized non-intrinsically safe circuits in a potentially explosive
atmosphere, sparks can ignite the surrounding atmosphere.
Only connect or disconnect energized non-intrinsically safe circuits in the absence
of a potentially explosive atmosphere.
Danger!
Danger to life from using damaged or repaired devices.
Using a defective or repaired device can compromise its function and its electrical safety.
Do not use a damaged or polluted device.
The device must not be repaired, changed or manipulated.
If there is a defect, always replace the device with an original device from Pepperl+Fuchs.
Danger!
Danger to life from electric shock
Working on live parts at voltages higher than 50 V AC or 120 V DC can result in electric shock.
1. De-energize the device.
2. Secure the circuit against reconnection.
3. Verify that the device is de-energized at all poles.
4. Provide protection from adjacent live parts, if present.

Other manuals for Pepperl+Fuchs KCD2-SCS-Ex2.SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pepperl+Fuchs KCD2-SCS-Ex2.SP and is the answer not in the manual?

Pepperl+Fuchs KCD2-SCS-Ex2.SP Specifications

General IconGeneral
BrandPepperl+Fuchs
ModelKCD2-SCS-Ex2.SP
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals