Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) 400 / 460 V, 3~ | 086100125 29/66
4.5 Assembly
WARNING
Risk of injury!
Risk of injury for persons due to the heavy weight of the units!
The total weight must be observed when transporting the unit.
Observe the weight according to section "Dimensions", Page 23.
Always transport the unit with several persons or suitable lifting gear.
Use personal protective equipment.
4.5.1 General
Ensure that the following general requirements are met for safe and reliable operation of the cooling units:
C
hoose an installation site for the switch cabinet that ensures adequate ventilation of the cooling unit. The minimum
distance of units from each other and from the wall is 200 mm.
Installations in the switch cabinet must not obstruct air circulation.
Secure switch cabinet against tilting.
Make sure that any hinges can bear the extra weight with cooling unit.
The cooling unit can be installed with or without an external unit cover.
Protect the installation site from heavy soiling using covers.