FL SWITCH 2000 / FL NAT 2000
96 / 226
PHOENIX CONTACT 108997_en_04
Interface: Ethernet (RJ45)
Number of interfaces 6
Connection method RJ45
Note on the connection method Auto negotiation and autocrossing
Transmission physics Copper
Transmission speed 10/100 Mbps
Transmission length 100 m (per segment)
Interface: Ethernet FO
Number of interfaces 2
Connection method ST
Transmission physics Single-mode fiberglass
Transmission speed 100 Mbps (full duplex)
Transmission length 36000 m (fiberglass with F-G 9/125 0.36 dB/km)
Transmission length 32000 m (fiberglass with F-G 9/125 0.4 dB/km)
Transmission length 26000 m (fiberglass with F-G 9/125 0.5 dB/km)
Wavelength 1300 nm
Supply voltage
Supply voltage 24 VDC (redundant)
Residual ripple 3.6 V
PP
(within the permitted voltage range)
Supply voltage range 9 VDC ... 57 VDC
Typical current consumption 235 mA (at U
S
= 24VDC and 25°C ambient temperature)
Max. current consumption 1.5 A (U
S
= Min, T
amb
= Max, DO
I
= Max)
Maximum power dissipation for nominal condition 6.75 W (U
S
= Min, T
amb
= Max, DO
I
= Max)
Test section for one minute 500 VDC
Mechanical tests
Mechanical tests Free fall in accordance with EN61131-2
Vibration (operation) in acc. with IEC 60068-2-6: 5g, 150 Hz
Vibration (storage/transport) 5g, 150 Hz, in acc. with IEC 60068-2-6
Shock (operation) 30g (EN60068-2-27)
Conformity with EMC directives
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Conducted noise emission EN 61000-6-2 EN 61000-6-4 (conducted interference) Class A
Interference emission EN 61000-6-2 EN 61000-6-4 (interference) Class A
Immunity to burst EN 61000-6-2 EN 61000-4-4 (EFT burst) Criterion A
Immunity to EF EN 61000-6-2 EN 61000-4-3 (electromagnetic fields) Criterion
A
Immunity to ESD EN 61000-6-2 EN 61000-4-2 (ESD) Criterion B
Immunity to surge EN 61000-6-2 EN 61000-4-5 (surge) Criterion A
Immunity to conducted interference EN 61000-6-2 EN 61000-4-6 (line noise immunity) Criterion A