Note: The direction of the perimeter
seal should be so the outside
overlap is pointing in the direction
of rotation. (If you have questions,
contact Phoenix.)
5. Removetheolddividerseal.
Installnewdividersealusing
originalmetalscrewsand
sealsretainers.(RefFigureB).
Figure A
Troubleshooting Guide
Trouble Probable Fault Probable Cause Corrective Action
 Powerandcontrolfailure 1.Mainpoweroff Checklineandmainpowersupply
2.Controlpoweroff
a.Controlcircuitfuseblown a.Replacefuse
b.Faultycontroltransformer b.Replacetransformer
c.Controlswitchopen c.Closeorreplaceswitch
d.Humidistatsatised d.Turndowntolowersetpoint
e.Faultycontrolelements e.Checkandrepairorreplaceasreq’d
Powerormechanical 1.Blownmotorfuse Replacecontrolcircuitfuse
failure 2.BadContactor Repairorreplace
3.Burnedoutmotor Repairorreplace
4.Failuresoffanmotor Repairorreplaceasreq’d
Excessiveinltrationof 1.Excessiveunconditionedmake-upair Reducemake-upair
humidairintothe 2.Leakingductsand/orairhandlingequip. Sealleaks
controlledspace outsidecontrolledspace
3.Accessopeningstospacenotsealed Closeand/orseal
4.Spacenotvaportight Sealwithpaintand/orvaporbarrier
Faultyhumiditycontrols 1.Humidstat
a.Improperadjustment a.Readjust
b.Defective b.Replace
Inadequateairow 1.Excessivestaticpressureloss
a.Dirtylter a.Cleanorreplace
b.Obstructionatinlet,outletorducting b.Removeobstruction
c.Cloggeddesiccantmedia c.Removeandreplacemedia
(Highpressuredropacrossmedia)
Inadequateorno 1.Elementburnout Replace.
reactivationheat 2.Lowvoltage Correctpowersupply
3.Faultycontrolelements Check,repair,orreplace
Airsealsandgaskets 1.Airleakageintodehumidier Replacepanelgasketsandseals
2.Airbypassingmediaorleakingseals Checkmediaposition,replaceseals
Ineffectivedesiccant 1.Mediadrivefailure
media a.Belt a.Repairorreplace
b.Motor b.Repairorreplace
2.Damageddesiccantmedia Repairorreplace
3.Contaminateddesiccant Cleanorreplacerotor
Divider Seals
6
www.UsePhoenix.com • sales@UsePhoenix.comToll-Free 1-800-533-7533
Figure B
Seal Clamp
Perimeter Seal
Unit stopped
(Fan off No
Heater)
Fan off (heater
functions)
Unit running but
humidity rises
9.4 Troubleshooting