PNOZ X4
Operating Manual PNOZ X4
19894-EN-07
19
Times 774730 774731 774734
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms 15 ms
With E-STOP max. 30 ms 30 ms 30 ms
With power failure typ. 50 ms 55 ms 55 ms
With power failure max. 70 ms 80 ms 80 ms
Recovery time at max.
switching frequency 1/s
After E-STOP 50 ms 50 ms 50 ms
After power failure 100 ms 100 ms 100 ms
Waiting period with a
monitored start 250 ms 150 ms 150 ms
Min. start pulse duration
with a monitored start 30 ms 30 ms 30 ms
Supply interruption before
de-energisation 20 ms 20 ms 20 ms
Simultaneity, channel 1
and 2 max.
Environmental data 774730 774731 774734
Climatic suitability EN 60068-2-78 EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during op-
eration Not permitted Not permitted Not permitted
EMC EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
Vibration
In accordance with the
standard EN 60068-2-6 EN 60068-2-6 EN 60068-2-6
Frequency 10 - 55 Hz 10 - 55 Hz 10 - 55 Hz
Amplitude 0,35 mm 0,35 mm 0,35 mm
Airgap creepage
In accordance with the
standard EN 60947-1 EN 60947-1 EN 60947-1
Overvoltage category III / II III / II III / II
Pollution degree 2 2 2
Rated insulation voltage 250 V 250 V 250 V
Rated impulse withstand
voltage 4 kV 4 kV 4 kV
Protection type
Mounting area (e.g.
control cabinet) IP54 IP54 IP54
Housing IP40 IP40 IP40
Terminals IP20 IP20 IP20

Other manuals for Pilz PNOZ X4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pilz PNOZ X4 and is the answer not in the manual?

Pilz PNOZ X4 Specifications

General IconGeneral
Supply Voltage24 V DC
Contacts3 N/O, 1 N/C
Width45 mm
Depth121 mm
MountingDIN rail
PL according to EN ISO 13849-1PL e
Category according to EN 954-14
SIL according to IEC 61508SIL 3
Max. switching current6 A
Protection classIP20
Operating Temperature-10 °C to +55 °C
Stop Category0
SIL CL according to EN IEC 62061SIL CL 3
Number of safe inputs2
Number of safe outputs3
Operating temperature range-10 °C to +55 °C