POLYCOM REALPRESENCE COLLABORATION SERVER V.8.6 APPLIANCE EDITION INSTALLATION
INSTALLING THE REALPRESENCE COLLABORATION SERVER (RMX) 4000
P
OLYCOM REALPRESENCE COLLABORATION SERVER GETTING STARTED GUIDE 39
3. After removal, attach the 23” brackets as provided in the Rack Installa-
tion Accessories kit, and re-install the handles to the 23” brackets, as
shown in the figure below.
Figure 1-17: Installing the handles and brackets & detailed rear view of 23”
bracket attachment
4. Mount the RealPresence Collaboration Server (RMX) 4000 on top of the
rack brackets using the blades or place it on a rack mount shelf with
chassis runners.
5. Fasten the RealPresence Collaboration Server (RMX) 4000 to the rack
with eight screws into the holes provided on the RealPresence Collab-
oration Server (RMX) 4000 front as shown in figure above.
ADDITIONAL INFORMATION: Rack mounting screws must be supplied by the rack
manufacturer.
The airflow of the RealPresence Collaboration Server (RMX) 4000 is from right
to left. Be sure that the areas on the left and right side of the system are clear
for proper ventilation.
Ground connection
When the unit is installed on a rack, the rack must be properly grounded to the
central office ground. The rack must be grounded with two-hole compression-type
connectors using copper conductors (tinned or untinned). Wire, bus bar or
braided strap connectors are acceptable.
The procedures of reverse mounting RealPresence Collaboration Server (RMX)
4000 from 23” brackets to 19” brackets are the same with the procedures
described above.
Connect the RealPresence Collaboration Server (RMX) 4000 to Power
Sources
You can connect either an AC or a DC power according to the power system
required at your site: