40
(2)
Refer to the table below for minimum copper wire sizing and ratings.
Voltage
Rating
Temp.
Class
Gauge
AC/Ground
600V
75°C/167°F
2AWG (33.6mm2)
PV/Battery
600V
75°C/167°F
10AWG (5.26mm2)
RSD Option 2
/12Vdc/AFCI
Communication
30V
60°C/140°F
24AWG (0.204mm2)
Ethernet
30V
60°C/140°F
Standard Ethernet cable
(3)
Refer to the table below for minimum external circuit breaker sizing and
ratings.
Voltage Rating
Current Rating
AC
600V
100A
PV
600V
30A
RSD Option 2
30V
1A
NOTE: If smaller-size wires and breakers are to be used for AC connection, grid
output current can be configured via the APP. Please contact POMCube to
confirm your configurations.
(4)
Connect iCAN NetZero Plus to ground (Torque: 3 m). Ensure installation is
compliant with local and national electrical codes.