6.6 PFC-7500/PFC-7501 Power Requirements
During AC power failure, the PFC-7500/PFC-7501 panels, and all auxiliary devices connected to the panels, draw their
power from the battery. All devices must be taken into consideration when calculating the battery standby capacity.
Below is a list of the power requirements of the PFC-7500/PFC-7501 panels. Add the additional current draw of Potter
keypads, smoke detectors, and any other auxiliary devices used in the system for the total current required.
6.7 PFC-7500/PFC-7501 Standby Battery Calculations
Standby Battery Power Calculations Standby Current Alarm Current
PFC-7500/PFC-7501 Panel
Relay Outputs 1-2 (ON)
Active Zone 1
Active Zones 2-5
521B/BXT Smoke Detectors
SLR-835B Smoke Detectors
Other 2-Wire Smoke Detectors
Bell Output (600mA Max.)
Qty __1___x
Qty ______x
Qty ______x
Qty ______x
Qty ______x
Qty ______x
50mA
30mA
3.3mA
4mA
0.070mA
0.070mA
0.1mA
______mA
______
______
______
______
______
______
______
Qty __1___
Qty ______x
Qty ______x
Qty ______x
Qty ______x
Qty ______x
50mA
30mA
3.3mA
4mA
0.070mA
0.070mA
0.1mA
______mA
______
______
______
______
______
______
______mA
TAM Trouble Annunciator Module 17mA ______ 17mA ______
RA-7630 Remote Fire Command Center Qty ______x 63mA ______ Qty ______x 92mA ______
RA-7692 Fire Security Command Keypad Qty ______x 30mA ______ Qty ______x 70mA ______
714 Zone Expansion Module
Active Zones (EOL Installed)
Qty ______x
Qty ______x
7mA
1.6mA
______
______
Qty ______x
Qty ______x
7mA
*2mA
______
______
715 Zone Expansion Module
Active Zones (EOL Installed)
Smoke Alarms
Qty ______x
Qty ______x
Qty ______x
7mA
4mA
.1 mA
______
______
______
Qty ______x
Qty ______x
Qty ______x
7mA
*30mA
.1mA
______
______
______
SNM Style W Notication Module Qty ______x 45mA ______ Qty ______x 76mA ______
Aux. Powered Devices on Terminals 7 and 6
Other than Keypads
______mA ______mA
Total Standby
Total Standby______mA x number of Standby Hours needed
Total Alarm
*Based on 10% of active zones in alarm
______mA
______ =
______mA
+
Total
Total Alarm _______mA
_________mA-hours
_________mA-hours
_________mA-hours
X 0.0001
= ________Amp-hrs Required