11.1 Description
Terminals 15 to 22 are the Class B (Style A) re zones on the PFC-7500/PFC-7501 panels. These zones are suitable for
connecting powered or non-powered re devices. For programming purposes, these zones are designated 2 to 5. The
maximum line impedance is 100 Ohms. The zone congurations on terminals 15 to 22 are described below:
Terminal Function Terminal Function
15 Zone 2 voltage sensing 16 Zone 2 negative
17 Zone 3 voltage sensing 18 Zone 3 negative
19 Zone 4 voltage sensing 20 Zone 4 negative
21 Zone 5 voltage sensing 22 Zone 5 negative
11.2 Operational Parameters
The Class B (Style A) zones on the PFC-7500/PFC-7501 panels can detect three conditions: open, normal, and short. Each
zone terminates with a Model 309, 3.3k Ohm EOL resistor (provided with the panel) and is rated for 53mA at 12 VDC.
The compatibility identier for use with 2-wire smoke detectors is: A.
11.3 Zone Response Time
A condition must be present on the zone for at least 500 milliseconds before it is detected by PFC-7500/PFC-7501
panels. Only use detection devices that are rated for use with this delay.
11.4 Compatible 2-Wire Smoke Detectors
The table below lists detectors meeting the compatibility requirements for use with the Class B (Style A) zones on the
PFC-7500/PFC-7501 re panels. Do not mix detectors from different manufacturers on the same zone.
Manufacturer Model
Detector
ID
Base Base ID
# of
Detectors
Detection Systems DS250 B MB2W A 10
Detection Systems DS250TH, DS250HD B MB2W, MB2WL A 10
Detection Systems DS282, DS282TH B 10
Hochiki SLK-12 HD-4 HSB-12-1, HSB-12-1N HB-80 20
Potter/Hochiki SLK-835, SLK-835H HD-5 HSB-200, HSB-200N HB-55 7
Potter/Hochiki SLR-835 HD-3 NS6-100 HB-55 7
Potter/Hochiki SLR-835B HD-6 7
Sentrol/ESL 429AT, 521B, 521BXT S09A 12
System Sensor 1100, 1400 STD 10
System Sensor 1151 STD B110LP 10
System Sensor 1451, 2451TH STD B401, B401B 10
System Sensor 1451DH STD DH400 10
System Sensor 2100, 2100T STD 10
System Sensor 2400, 2400AT,
2400AIT, 2400TH
STD 10
System Sensor 2451 STD B401, B401B, DH400 10
Class B (Style A) Fire Zones