Domestic water storage tank
(1)
Prog. no. Level Standard value
Type of charging
1: Recharging | 2: Full charging | 3: Full charging legio | 4: Full charg 1st time
day | 5: Full charg 1st time legio
5022 E Full charging
Switching diff 5024 E 4 °C
Charging time limitation 5030 E 120 min
Discharging protection
0: Off | 1: Always | 2: Automatically
5040 E Automatically
Discharg protec after charg
Off | On
5042 Off
Charging temp max 5050 E 69 °C
Recooling temp 5055 E 80 °C
Recooling collector
0: Off | 1: Summer | 2: Always
5057 E Off
El imm heater optg mode
1: Substitute | 2: Summer | 3: Always
5060 E Substitute
El immersion heater release
1: 24h/day | 2: DHW release | 3: Time program 4/DHW
5061 E DHW release
El immersion heater control
1: External thermostat | 2: DHW sensor
5062 E DHW sensor
Automatic push
Off | On
5070 E On
Excess heat draw
Off | On
5085 E On
With buffer
No | Yes
5090 E Yes
With prim contr/system pump
No | Yes
5092 E Yes
With solar integration
No | Yes
5093 E Yes
Pump speed min 5101 E 0 %
Pump speed max 5102 E 100 %
Speed Xp 5103 E 15 °C
Speed Tn 5104 E 60 s
Speed Tv 5105 E 5 s
Transfer strategy
0: Off | 1: Always | 2: DHW release
5130 E Always
Interm circ boost recharging 5139 E 5 °C
Intermediate circuit boost 5140 E 2 °C
Excess interm circ temp max 5141 E 2 °C
Flow setp compensation delay 5142 E 30 s
Flow setp compensation Xp 5143 E 50 °C
Flow setp compensation Tn 5144 E 30 s
Flow setp compensation Tv 5145 E 30 s
Full charging with B36
No | Yes
5146 E No
Min start temp diff Q33 5148 E -3 °C
Excess interm circ temp del 5151 E 30 s
(1) Parameters depend on the hydraulic System!
Configuration Prog. no. Level Standard value
Heating circuit 1
Off | On
5710 C On
Heating circuit 2
Off | On
5715 C Off
Heating circuit 3
Off | On
5721 C Off
9 Settings
70 Paramount five 30 – 115 7703046 - 01 - 23072018