34 GTS Series Uninterruptible Power Manager
Noise Rejection and Isolation
With unit under power and an ANSI/IEEE C62.41 Category A impulse
applied either normal mode or common-mode at the input, the noise
output voltage will be less than 10 volts normal mode and 0.5 volts
common-mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM)
Surge Voltage Withstand
Tested under power to ANSI/IEEE C62.41 Category A & B (formerly
IEEE587-1980) - Category A 6000V/200A, 0.5 usec. risetime, 100 kHZ
decay, Category B 6000V/500A, 0.5 usec. risetime, 100 kHZ decay.
Voltage Manager Operation
Boosts voltage when main drops to 90% of nominal. Bucks voltage when
main rises to 110% of nominal.
Safety Agency Listings
North American models to UL1778. International models are UL and cUL
listed. All models for international use carry the CE mark.
EMC Conformance
All Voltage Models: FCC Part 15 J Class A
International Voltage Models: FCC Part 15 J Class A
EN 55022 Class B/CISPR 22, EN 50091-2, IEC 61000-3-2