2261V102-UK 13
4.3 UI - Selection of current or voltage output
See the hardware programming for correct jumper setting. Possible
selections are:
001 = Current output in the range 0...10 mA
002 = Current output in the range 0...20 mA
003 = Voltage output in the range 0...500 mV
004 = Voltage output in the range 0...1000 mV
005 = Voltage output in the range 0...5 V
006 = Voltage output in the range 0...10 V
4.4 rEP - Setting of response time
Valid selections are 0.0...999 s. If the set response time is < 0.06 s, the
response time will be 0.06 s.
5.0 APP - APPLICATION SELECTION
5.1 tAR - Selection of taring type
Possible selections are tLO - 0% taring enable, tHI - 100% taring enable,
or dtA - taring disabled.
If tLO is selected, activating the
3 key for more than 2 s or activating the
digital input will tare the input signal to 0%.
If tHI is selected, activating
3 for more than 2 s or activating the digital
input will tare the input signal to 100% (max.).
The 2 types of taring can be used for filling or emptying respect ively.
If a 0% (tLO) taring is selected, the analogue input will show 0% after
taring. If a 100% (tHI) taring is selec ted, the input will show 100% after
taring corresponding to tara + net weight = gross weight.
Taring is either from the digital input or from front.
5.2 dIN - Selection of digital input type
Possible selections are:
PnP = mechanical contact or open collector transistor connected to +24
VDC.
nPn = mechanical contact or open collector transistor connected to gnd.
5.3 SUP - Setting of supply voltage for transducer
Valid selections are 5.0...13 VDC.
Description of functions (selection of application)