2 2261V102-UK
mV TRANSMITTER
• Load cell amplifier
• mV to current / voltage conversion
• Front-programmable / LED display
• Relative calibration of input span
• NPN / PNP input for external taring
• Supply for standard transducers
----------------------------------------------------------------------------------------------------------------
SUPPLY:
Supply voltage: 24 VDC
Transducer supply: 5...13 VDC
----------------------------------------------------------------------------------------------------------------
INPUT RANGE:
Measurement range: -40...100 mV
Taring input: PNP / NPN / front key
----------------------------------------------------------------------------------------------------------------
OUTPUT RANGE:
Current output: 0...20 mA
Voltage output: 0...10 V
----------------------------------------------------------------------------------------------------------------
Applications
Tank filling and draining
Weighing with a taring function
Measurement of cable tensile force
Level control
Signal conversion / amplification
The 2261 converts bipolar mV signals from transducers supplied directly by the
module to standard current / voltage signals. The 2261 is suitable for load cell
applications. By way of the relative calibration function the scale can be tared,
i.e. 0 and 100% calibrated without the need of the equivalent load. By way of
the taring function the measured range is set to either 0% when filling or 100%
when draining.