Common specifications:
Supply voltage, DC .................................................. 19.2...31.2 VDC
Max. consumption .................................................... 3 W (2 channels)
Fuse ............................................................................... 400 mA SB / 250 VAC
Isolation voltages, test / operation:
Inputs / outputs / supply ............................ 2.6 kVAC / 300 VAC reinforced
Output 1 to output 2 .................................... 1.5 kVAC / 150 VAC reinforced
Status relay to supply .................................. 1.5 kVAC / 150 VAC reinforced
Communications interface ................................... Communication enabler 4511 /
Programming front 4501
Response time for cable fault ............................ < 200 ms
Calibration temperature ........................................ 20...28°C
Auxiliary supplies:
NAMUR supply .......................................................... 8 VDC / 8 mA
Inputs:
Sensor types:
NAMUR according to ..................................... EN 60947-5-6
Mechanical switch with
series (R
s
) and parallel (R
p
) resistance:
R
s
.......................................................................... Nom. 750 Ω
R
p
.......................................................................... Nom. 15 kΩ
Frequency range ...................................................... 0...5 kHz
Min. pulse length ..................................................... > 0.1 ms
Input resistance........................................................ Nom. 1 kΩ
Trig level, signal ....................................................... < 1.2 mA, > 2.1 mA
Trig level, cable fault .............................................. < 0.1 mA, > 6.5 mA
Outputs:
Relay outputs:
Status relay:
Max. voltage ..................................................... 125 VAC / 110 VDC
Max. current ...................................................... 0.5 A AC / 0.3 A DC
Max. power........................................................ 62.5 VA / 32 W
Relay outputs:
Max. switch frequency ................................. 20 Hz
Max. voltage ..................................................... 250 VAC / 30 VDC
Max. current ...................................................... 2 A AC / 2 A DC
Max.power ......................................................... 500 VA / 60 W
Opto, NPN outputs:
Max. switch frequency ................................. 5 kHz
Min. pulse length ............................................ > 0,1 ms
Max. load, current / voltage. ...................... 80 mA / 30 VDC
Voltage drop at 80 mA ................................. < 2.5 VDC

Table of Contents

Other manuals for PR electronics 9202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PR electronics 9202 and is the answer not in the manual?

PR electronics 9202 Specifications

General IconGeneral
BrandPR electronics
Model9202
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals