Click Recipe to enter the recipe setting inteace, and click Peristaltic pump to set the working
status, working type, and working time ratio of the peristaltic pump;
Set the working type of each peristaltic pump, including EC, pH+ or pH-, the pump closest to
the screen is Pump1, and so on. Note: Pump1 defaults to pH type.
If the addition ratio of the nutrient solution in each channel is not in a 1:1 relationship, you need
to set the working time ratio of the single feeding time of the EC pump for each nutrient solution,
and the system will use the feilizer with the highest ratio to match the feilizer time as a reference.
Examples are as follows:
If single Dosing time dosing=10s, Mix time=30s, there are 3 feilizers and 1 pH-, the ratio of
feilizer A:B:C is 1:2:3; then feilizer C corresponds to the pump within a pump operation cycle (
dosing+Mix=40s, each pump is the same and xed after setting), work for 10 seconds (ratio:100%),
stop for 30 seconds; the pump corresponding to B feilizer works 10*2/ 3=6.66 seconds
(ratio:66.6%), stop for 33.33 seconds; the pump corresponding to feilizer A works for 10*1/3=3.33
seconds (Ratio:33.3%) in one pump operation cycle, stop for 36.66 seconds.
12