Click Recipe to enter the recipe setting inteace, and click Peristaltic pump to set the working
status, working type, and working time ratio of the peristaltic pump;
Set the working type of each peristaltic pump, including EC, pH+ or pH-, the pump closest to
the screen is Pump1, and so on. Note: Pump1 defaults to pH type.
If the addition ratio of the nutrient solution in each channel is not in a 1:1 relationship, you need
to set the working time ratio of the single feeding time of the EC pump for each nutrient solution,
and the system will use the feilizer with the highest ratio to match the feilizer time as a reference.
Examples are as follows:
If single Dosing time dosing=10s, Mix time=30s, there are 3 feilizers and 1 pH-, the ratio of
feilizer A:B:C is 1:2:3; then feilizer C corresponds to the pump within a pump operation cycle (
dosing+Mix=40s, each pump is the same and xed after setting), work for 10 seconds (ratio:100%),
stop for 30 seconds; the pump corresponding to B feilizer works 10*2/ 3=6.66 seconds
(ratio:66.6%), stop for 33.33 seconds; the pump corresponding to feilizer A works for 10*1/3=3.33
seconds (Ratio:33.3%) in one pump operation cycle, stop for 36.66 seconds.