Control Output Signals
The output signal from the controller feature is either a DC voltage or current depending on the
terminals used.
Voltage:
The voltage is a 0 –10V signal where:
5v is provided when the measured variable is at the set point value.
ABOVE 5V when the process variable is LESS than the set point.
BELOW 5V when the process variable is GREATER than the set point.
Current:
The current is a 4-20mA signal where:
12mA is provided when the measured variable is at the set point.
ABOVE 12mA when the process variable is LESS than the set point.
BELOW 12ma when the process variable is GREATER than the set point.
67