19
5.4 Grounding
Grounding cables should be 6 AWG or higher yellow-green cables. After
connection, the resistance from battery grounding point to Ground
connection point of room or installed place should be less than 0.1 Ω.
1) There should be direct metal-to-metal contact between
the module surface and the rack surface. If painted racks
are used, the paint should be removed from the
corresponding place.
2) Connect a grounding cable to the grounding point of
the modules.