[ Table 9-2 : Battery Operation General Events List ]
WEB Display HMI Display Description Measures
Power reset of the system is required.
If the symptom still occurs after reset, repair
of BMS or PCS Control Board is necessary.
BAT5 Additional
Protection
BAT5 ADD PB48P
When the maximum cell temperature is
above protection level, thus terminating the
system. Automatically returns to normal when
the maximum cell temperature goes below
the limit value.
BAT5 Cell Over Temp
Protection
BAT5 CEL OT
P
B46P
When the minimum cell or rack voltage is
below protection level, thus terminating the
system. Automatically returns to normal when
the minimum cell or rack voltage goes above
the limit value.
BAT5 Cell or Rack
Under Voltage
Protection
BAT5 CEL UV
P
B45P
Power reset of the system is required. If the
symptom persists after reset, replace the
cable connecting the Battery pack and the
INVERTER. After replacement, repair of BMS
or PCS Control Board is necessary.
BAT5 Communication
Protection
BAT5 COM PB47P
99 I Problem Confirmation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Q CELLS Q.SAVE G2 4kWh B1.1.1 and is the answer not in the manual?

Q CELLS Q.SAVE G2 4kWh B1.1.1 Specifications

General IconGeneral
BrandQ CELLS
ModelQ.SAVE G2 4kWh B1.1.1
CategoryInverter
LanguageEnglish

Related product manuals