Alarm LED is lit 18.No start time. All start times have been removed. (The factory default program is in effect:
Program A at 8:00AM.)
Enter at least one start time and set the dial back to AUTO. The LED will turn off.
19.No run times. The default 10-minute run time for all active valves has been removed. Enter a run
time for at least one active valve and set the dial back to AUTO. The LED will turn off.
20.Seasonal adjust is at 0%. The seasonal adjust % value has been set to zero. Enter a seasonal adjust value and
set the dial back to AUTO. The LED will turn off.
21.Shorted station. A short circuit in the solenoid or valve wiring has disabled the station. See correction
for Cause #10.
TROUBLESHOOTING
SYMPTOM POSSIBLE CAUSE CORRECTION