3. HARDWARE
3.3. Whatdatacanthesensornodecollect?
The sensor node is provided with 24 input points which allows for input from various sensors.
Power consumption can be monitored with a current transformer. The sensor node is provided with
2 current transformer inputs, CT1 (3.5 mm power socket) and CT5.
Current transformers with a secondary rating of 1A (primary rating lower than 60A) must be con-
nected to the 3.5 mm power socket on the sensor node. Current transformers with a secondary
rating of 5A (primary rating higher than 60A) must be connected to the connectors 5- and 5+ on
the sensor node.
External temperature can be monitored with a platinum sensor. The sensor node is provided with 1
platinum sensor input point: PT100. The platinum sensor input can monitor external temperatures
between 6–150 °C (43–302 °F).
The sensor node is provided with 8 digital input points: DI1 – DI8. Digital inputs can monitor on and
ostatesinthemachine.Examplesofonandostatesisifthemachineisrunningorstopped,if
an emergency stop is active or inactive, or if the machine is opened or closed.
The sensor node is provided with 2 analogue input points: AD1 and AD2. Analogue input can be
used to monitor variable values in the machine. Examples that can be monitored by analogue input
is the regrind level in a container, the setting of a potentiometer, or the speed of a band conveyor.
Digital input
I/O-link
Digital output24V DC
24V DC
CT1 / CT5
Analogue
input
External
temperature
Digital input
ModBus
24V DC Main supply
24V AC Main supply
230V