Programming Guide
Marathon MR Rev. E2 04/2011 47
9.5 Command List
Table describes the commands available for 2-way communications.
000.0–299.9 sec
(300 s = )
Relay alarm output control
Target temp – 1-color narrow
000.0–299.9 sec
(300 s = )
Notes:
(1) Commands may appear as Polled for (queried), Burst string item,
Set command, or Notification.
(2) n = number, X = uppercase letter.
(3) see section 9.3.2 Burst Mode, Seite 45
(4) Setting Peak Hold cancels Average, and vice-versa.
(5) The sensor restarts after a baud rate change. (Command is not
allowed in broadcast mode.)