MPAX PERSONALITY MODULE SELECTOR GUIDE FOR LPAX
Our large displays have various input options, determined by the installation of a MPAX personality module. These MPAX
modules are based on standard PAX panel meters, and use the same data sheet as the PAX meter for specifications and wiring.
About the MPAX Input Modules
The MPAX Module serves as the input to the LPAX Display. There are several different modules to cover a variety of inputs. The
MPAX module provides input scaling which allows the LPAX to display most any engineering unit. Once the MPAX is inserted into
the LPAX, the unit has the same functions and capabilities of our PAX Series Intelligent Panel Meters. A full set of PAX
programming instructions will be included with the MPAX Module.
Note: The MPAX provides the operating power for the LPAX, therefore you must select either the AC or DC MPAX corresponding
with your application and available power.
Selecting Your Display Components
To build a complete display unit, you will need an LPAX and an MPAX Input Module. The LPAX is only a display and will not
operate without an MPAX Module. Please use the following chart to identify the appropriate MPAX Module (including supply
power) and LPAX Display that will satisfy your application.
MPAX Modules for LPAX5 (Analog units)
MPAX Modules for LPAX6 (Digital units)
MPAX MODULES *
SIGNAL TYPE INPUT RANGES
85-250 VAC
11 to 36 VDC/ 24 VAC
LPAX DISPLAYS
Universal DC Inpu ts
DC Voltage 200 m V, 2 V, 20 V, 300 V
DC Current 200 µA, 2 mA, 20 mA, 200 mA, 2 Amp
Resistance 100 ohm, 1000 ohm, 10 K ohm
MPAXD000 MPAXD010 LPAX0500
Process Inpu ts 0-20 mA or 0-10 VDC MPAXP000 MPAXP010 LPAX0500
Temperature Inpu ts MPAXT000 MPAXT010 LPAX0500
Strain Gage/Load Cell 24 mV or 240 mV MPAXS000 MPAXS010 LPAX0500
True RMS AC
Voltage/Current
AC Voltage 200 m V, 2 V, 20 V, 300 V
AC Current 200 uA, 2 mA, 20 mA, 200 mA, 5 Amp
MPAXH000 N/A LPAX0500
SETPOINT
YES
MPAX MODULES*
YES
YES
SIGNAL TYPE
YES
85-250 VAC
11 to 36 VDC / 24 VAC
LPAX
DISPLAYS
Count/Rate/Serial Slave
COMMS
MPAXI000
MPAXI010
LPAX0600
Count
YES
MPAXC000 MPAXC010 LPAX0600
Rate
-
MPAXR000 MPAXR010 LPAX0600
Clock/ Timer
-
MPAXCK00
††
MPAXCK10
††
LPAXCK00**
YES
ANALOG
YES
-
-
-
REAL-TIME
CLOCK
-
-
-
YES
OPTIONAL PLUG-IN CARD COMPATIBILITY
YESTime r
MPAXTM00
††
MPAXTM10
††
LPAXCK00**
YES - -
MPAX Modules for LPAXDA (Dual Analog Unit)
MPAX MODULES *
SIGNAL TYPE INPUT RANGES
85-250 VAC
11 to 36 VDC/ 24 VAC
LPAX DISPLAY
Dual Process Inputs 0-20 mA or 0-10 VDC MPAXDP00 MPAXDP10 LPAXDA00
Thermocouples -T , E, J, K, R, S, B, N, C,
or Custom Scaling RTDs - 100 ohm Pt (platinum) 385/392,
120 ohm Nickel 672, or 10 ohm Copper 427

Questions and Answers

  • H
    Heidi HoffmanAug 15, 2025
    What to do if the red lion Measuring Instruments display is jittery?
    • M
      Monica HollandAug 15, 2025
      If the display is jittery, increase Module 1 filtering, rounding, and input range. Also, verify that the wiring follows EMC installation guidelines.
  • F
    fmendezAug 18, 2025
    What to do if the red lion Measuring Instruments shows incorrect input display value?
    • D
      Denise SalazarAug 18, 2025
      If the input display value is incorrect, check the following: * Module 1 programming * Input Range Jumper position * Input connections * Input signal level * Module 4 Display Offset is zero Press DSP for Input Display. If the problem persists, perform Module 9 Calibration.
  • W
    Wesley FloydAug 21, 2025
    What does OLOL mean on my red lion Measuring Instruments display?
    • J
      Justin ConnerAug 21, 2025
      If “OLOL” is displayed (SIGNAL HIGH), check Module 1 programming, the Input Range Jumper position, input connections, and the input signal level.
  • C
    Casey RoyAug 25, 2025
    What does ULUL mean on my red lion Measuring Instruments display?
    • D
      Dawn HillAug 25, 2025
      If “ULUL” is displayed (SIGNAL LOW), check Module 1 programming, the Input Range Jumper position, input connections, and the input signal level.
  • J
    john32Aug 27, 2025
    How to fix a program locked-out on red lion Measuring Instruments?
    • C
      Cesar KempAug 27, 2025
      If the program is locked-out, check the active (lock-out) user input and enter the security code when requested.
  • J
    Jessica PatelAug 30, 2025
    What to do if modules or parameters are not accessible on red lion Measuring Instruments?
    • B
      Benjamin NelsonAug 30, 2025
      If modules or parameters are not accessible, check the corresponding plug-in card installation.
  • S
    Stephanie AguilarSep 2, 2025
    What does error code Err 1-4 mean on red lion Measuring Instruments?
    • V
      Victoria GonzalezSep 2, 2025
      If you see error code Err 1-4, press the Reset KEY. If that doesn't clear the error, contact factory.
  • M
    Miguel LeonardSep 5, 2025
    How to fix max, min, tot locked-out on red lion Measuring Instruments?
    • J
      jessicahunterSep 5, 2025
      If MAX, MIN, or TOT is locked-out, check Module 3 programming.
  • C
    Charles AlexanderSep 8, 2025
    How to disable zero chop feature on red lion Measuring Instruments?
    • M
      Michael BerrySep 8, 2025
      To disable the zero chop feature, program Module 4 as Hi-t: 0.0 LO-t: 3271.1.
  • A
    Andrea CochranSep 12, 2025
    How to troubleshoot no display on a red lion Measuring Instruments?
    • T
      Terri BellSep 12, 2025
      To troubleshoot a 'no display' issue, check the power level and power connections.

Summary

MPAX Module Selection Guide

PAX Series Panel Meters Overview

Safety Summary

Essential safety precautions for installation and operation of the meter.

MPAX Module Models

Installation and Jumpers

Installing the Meter

Instructions for physically installing the meter into a panel.

Setting the Jumpers

Guide to setting jumpers for various MPAX module types.

Wiring Procedures

Wiring Overview and EMC Guidelines

General wiring practices and EMC installation guidelines.

Input Signal Wiring

Detailed wiring diagrams for various input signal types.

User Input and Function Key Operations

Programming Modules

Module 1: Signal Input Parameters

Configuration of input ranges, scaling, filtering, and offsets.

Module 2: User Input;Function Key Parameters

Programming user inputs and function keys for specific actions.

Module 3: Display;Program Lock-Out

Settings for locking display items and programming modes.

Module 9: Factory Service Operations

Operations for display intensity, factory defaults, and calibration.

Calibration and Service Operations

Input Calibration Procedures

Step-by-step calibration instructions for various input types.

Analog Output Card Calibration

Procedure for calibrating the analog output card.

Troubleshooting

LPAX Display Specifics

LPAX Display Installation

Instructions for installing the LPAX display into a panel.

red lion PAXS Series Specifications

General IconGeneral
Brandred lion
ModelPAXS Series
CategoryMeasuring Instruments
LanguageEnglish