— English Servitec 35-95 with
— 18.12.2019 - Rev. A
Make-up degassing
• Usage:
– For gas-rich water from the make-up.
– For summer operation when the circulating pumps of the facility
system are shut down, see chapter 8.1.4 "Summer operation" on
page 17 .
– If the facility system water is not to be degassed.
• Activation:
– Automatic activation occurs at every water make-up.
• During continuous degassing.
• During interval degassing.
• Times:
– The make-up water is degassed for as long as it is supplied, see
chapter 9.1.1 "Customer menu" on page 18 .
Note!
Manual activation of the degassing program takes place in the customer
menu.
9.1.5 Setting degassing programmes
1. Press "Settings".
– The controller switches to the setting area.
2. Press "Customer >".
– The controller opens the Customer menu.
3. Press "Degassing >".
– The controller switches to the selected area.
– Use the scroll bar to navigate "up" and "down" through the list.
4. Press "(012) Degassing programme".
– The controller opens the list of degassing programmes.
5. To select a menu item, press the "Up" or "Down" scroll bar until this menu
item is displayed.
• Press the desired button.
– "Continuous degassing" is selected in this example.
– Interval degassing is deactivated.
– Make-up degassing is deactivated.
• Confirm your selection with "OK".
Continuous degassing is activated.
6. Press "(013) Time, continuous degassing".
7. Set the time for continuous degassing.
• Use the "Left" and "Right" buttons to select the display value.
• Use the "Up" and "Down" buttons to change the display value.
• Confirm your entries with "OK".
The time for continuous degassing is set.
– Press "i" to display a help text for the selected area.
– Press "X" to cancel your input without saving the new settings. The
controller automatically opens again the list.
9.2 Messages
The messages indicate impermissible deviations from the normal operating state
of the Servitec. They are output either via the RS-485 interface or via two floating
message contacts.
The controller displays the messages with a help text. By selecting the fault
memory in the Customer menu, you display the last 24 messages. Message
causes can be eliminated by the operator or a specialist workshop. If required,
please contact the Reflex Customer Service.
Note!
Messages identified with "OK" must be confirmed with the "OK" button
on the display. The device operation is otherwise interrupted. The
readiness for operation is maintained for all other messages.
They are
necessary, you can set the output of messages via a floating contact in