REFUsol 20K-2T (853P020.200)
User manual
Figure 5-8: Removing AC waterproof cover diagram.
Step 2: Select the appropriate cable diameter according to table 5-1, process the
cable according to the following picture size requirements, and then pass through
PG waterproof joint.
R type terminal, Insulating sleeve,
RNBS14-6 (8awg). terminal shall not be exposed.
Figure 5-9 AC cable connection instruction diagram (1)
Step 3: After assembling the PG waterproof connector, connect the cable to the AC
terminal block L1, L2, L3, N, PE contacts, and fasten them (4~5 N · m). Tighten the
lock nut of PG terminal clockwise (7~8 N · m).